Fig. 1. Typical harmonic disturbance associated with PA firing for single and 3-phase loads
Reducing energy costs remains a key area of focus, and successful companies are finding ways to improve their competitiveness by concentrating investment in this area of their business. This article aims to highlight further savings, which can be made by paying careful attention to the way electrical energy is used and distributed around thermal processing equipment.

Fig. 2. Typical response from a 4 tap change control system
Electrical Heating for Industrial Furnaces
Energy MonitoringSince most of the metals supply and heat-treating process industry is audited, there is a need to record and store batch and process data. With the advent of simple communicating power metering equipment, it is a natural extension of the control system to embed plant energy usage into the stored records. Having access to energy data in real time and historic format allows users to evaluate the following:
- Instantaneous overall shop-floor power demand
- Instantaneous power demand for individual furnaces
- Energy usage against furnace loading
- Energy usage against plant utilization
- Fiscal costing against customer batches
- Plant priority for load shedding
Using wireless technology as a cost effective way to acquire and distribute energy information over Ethernet allows the data to be shared in real time between groups of internal management and engineering clients. Experience has shown that where users have access to energy data it has always been possible to define areas of savings.

Fig. 3. Optimized furnace cycle using proprietary algorithm
Except for the most complex heater loads, i.e. those element materials that have resistance change with temperature or complex transformer coupled loads, it is recommended that simple whole-cycle switching methods be employed to control electrical energy with thyristors.
The continuing use of Phase Angle (PA) cycle chopping for simple heaters, including modern SiC, causes disadvantages to users through poor power factor harmonic disturbance on the supply and RF interference around the installation. Figure 1 shows typical harmonic disturbance associated with PA firing for single and 3-phase loads. It can be seen from the diagrams that when switching the sine wave at 90 degrees a high proportion of odd harmonic current is reflected into the supply.
Poor power factor associated with phase angle firing is the principle concern for energy cost. Since most electrical installations are designed to operate near 50% output power at the nominal operating set point, the supply mains cycle will be chopped at the worst case of 90 degrees when operating in PA mode. Under these conditions the resultant power factor could be as low as 0.72 instead of above the desired level of 0.95.
Dependent on the metering type and the supply impedance, this could have a very detrimental effect on the billing value, adding 7-10% cost with no benefit to the process.
Two simple solutions can reduce or overcome the disadvantages associated with PA thyristor control.
- For installations where phase angle control cannot be avoided, using an electronic supply tap changer will automatically keep the power factor and supply disturbance to a minimum. Figure 2 shows typical response from a 4 tap change control system. Notice how the power factor is above 0.9 for most tappings at the critical 50% demand level compared to the fundamental curve, which shows 0.72 for 50% demand.
- For non-complex heater loads, it is possible to use any of the whole cycle firing modes, including single cycle and advanced single cycle switching methods, to satisfy the watts density loading and thermal mass characteristics of most common heaters while eliminating the poor power factor and harmonic problems.
Advanced single cycle can be particularly effective for shortwave infrared loads or for loads where it is desirable to minimize the effect of long burst of power on the elements. For element materials, which have a positive resistance/temperature coefficient, it is also possible to use intelligent thyristors to switch from phase angle firing to whole cycle firing when the element resistance increases to allow full mains volts to be impressed across the load.
Information is available from the supplier on the benefits of alternative thyristor switching methods for particular heater materials.

Fig. 4. Zone sequencing pattern
It has long been recognized that analysis of furnace power behavior can indicate furnace performance. Consumers are using power profile recognition to determine operational changes on their processing equipment against batch types.
A recent advance in online power monitoring for batch heat treatment cycles has produced a furnace power optimization solution for homogenization, annealing, normalizing and similar heat treatment processes. In this application, the point at which the temperature within the stock has become homogenous is recognized by a steady-state control algorithm acting on the derivative of power consumption. Clients are using this control system intelligence to recognize the point at which equilibrium is reached to shorten process times and improve plant utilizations. Eurotherm uses their proprietary algorithm to give customers this cost saving benefit without the need to include additional work piece monitor sensors.
Figure 3 shows curves associated with furnace and work piece temperature performance against the derivative of the energy used in the proprietary furnace energy optimization algorithm.

Fig. 5. Supply-switching pattern before and after load sharing
Where a heat treatment shop has a large installed base of electrically heated thermal processing equipment, it is often desirable to sequence the firing of individual furnace zones or independent furnaces to minimize the supply fluctuation. By using intelligent thyristor firing methods it is possible to limit the power surge and instantaneous supply loading associated with any installation through a selectable combination of firing patterns. In this mode, none of the zones are switched on simultaneously and individual furnace or zone power demands are synchronized to give a very even loading on the factory supply.
Figures 4 and 5 show a zone sequencing pattern and the overall effects on the supply by better distributing the load on the plant. The benefits allow clients to operate higher installed equipment base from the existing supply.
A further benefit can be obtained from this solution by setting a threshold on the smoothed power level to trap excursions of energy use through the site maximum demand point. Setting alarms on the threshold level can trigger prioritized load shedding, thus avoiding costly excess tariff penalties.

Fig. 6. Out-of-hours set point control automation
Using the intelligence of modern control systems it is possible to automate out-of-hours set point control for thermal-processing equipment. In the example shown in Fig. 6, the control system understands the dynamics of the furnace and can recognize the power required to maintain the standby set point and the power required to achieve the operating set point.
The controller has a user screen which allows the operator to enter the required duty set point and time for the furnace to be back at temperature. The controller uses the furnace tuning information and an internal real time clock to dynamically control unsupervised turn-up. Benefits allow much more consistent and repeatable energy savings through the use of out-of-hours furnace turndown.
For more information:Jim Tebbs is Heat Treat Business Development Manager for Eurotherm, Worthing, West Sussex, UK; tel: +1 44 (0) 7713 502534; US Office: (703) 443-0000 (ext 324); e-mail:jim.tebbs@eurotherm.co.uk; web:www.eurotherm.com/heat-treatmentfor information on energy saving control systems.